| Chemistry | Lithium iron phosphate (LFP), CATL EnerOne modules, 1C rated |
|---|
| Battery rack | 1164.8–1500 V DC (1331.2 V nominal); 280 A nominal |
|---|
| DC bus | 761–1200 V nominal operating range; 720–1500 V maximum |
|---|
| AC output | 480 V AC, 3-phase 3-wire, ±10%; 208 V auxiliary; 1203 A maximum output current |
|---|
| Power conversion | EPC Power CAB1000 PCS, UL 1741 SA/SB; 98.8% peak efficiency; power factor 100% active to 100% reactive; input current distortion <3% |
|---|
| Fault rating | 180 kAIC maximum fault current from the AC source |
|---|
| Overload | 116% for 5 min and 120% for 3 s at 40 °C and >65% load (brochure); manual states 115% for 2 s and 105% for 5 min [verify with Eaton] |
|---|
| Dimensions and weight (480 V) | Control cabinet 53.5 x 58.5 x 68.9 in, 1014 lb (brochure) / 1228 lb (manual) [verify]; PCS 39.9 x 64.6 x 87.6 in, 3173 lb; battery cabinet 50.9 x 51.6 x 89.8 in each, 7830 lb (brochure) / 7716 lb (manual) [verify]; 3-cabinet lineup approx. 251.7 in long |
|---|
| Environment | Outdoor installation only on pad or skid; -20 to 50 °C ambient (derated above 40 °C); NEMA 3R / IP54 system, IP66 battery enclosures; <75 dBA at 3 m; liquid-cooled PCS and batteries |
|---|
| Certifications | UL 9540 (system); UL 1741 SA/SB (PCS); UL 1973 and UL 9540A (battery); ISO 9001 manufacturing |
|---|
| NFPA 855 | 10 ft setback standard (3 ft with AHJ approval); integral fire-control panel with Novec 1230 suppression; fire-panel notification; front-door E-stop opens AC and DC contactors |
|---|
| Seismic | ICC-ES AC156: PCS at Sds 1.35 g, control cabinet at Sds 2.0 g; battery cabinets IEEE 693 by analysis |
|---|
| Domestic content | Integrated system TAA compliant; control cabinet and PCS Buy America compliant; batteries sourced outside the U.S. |
|---|
| Required transformer | 480:480 V double-shielded isolation transformer, wye primary / delta secondary, 300–1200 kVA, to meet IEEE 1547.4 grounding on an islanded system (not included) |
|---|
| Operating modes | Peak shaving (static setpoints; state-of-charge-based setpoints require a supervisory controller such as Eaton Power Xpert), time-of-use arbitrage, demand response, backup and islanding, black start, solar self-consumption, aggregation |
|---|
| Not a UPS | Open-transition system; pair with a UPS where uninterrupted power to critical loads is required |
|---|
| Communications | Modbus TCP, GSEC, Eaton Brightlayer remote monitoring; local fault and event logging |
|---|
| Design life | 10+ years at one full cycle per day (95% to 5% depth of discharge); multiple partial cycles or extreme ambient temperatures shorten life |
|---|
| Warranty | Eaton three-phase product warranty; term for xStorage not stated in brochure or FAQ [verify]; service plans from extended warranty to response-time agreements available |
|---|