The V4 Cabinet holds the power electronics for a Supercharger for Business site, delivering up to 1,200 kW shared across eight V4 posts at greater than 96% efficiency with no forced ventilation requirement. For design purposes the cabinet, not the post, sets the electrical scope: we size the utility service, transformer and switchgear for the cabinet's shared output and use Tesla's guidance that eight posts typically need under 1 MW to meet demand 99% of the time, which keeps the transformer order realistic. The 100 m cabinet-to-post limit lets us place the cabinet pad near the service entrance and away from customer parking. Tesla does not publish the alternating current (AC) input rating; we obtain it through the Tesla Design Engineer review during site design.
Quotes include the complete bill of materials — equipment, make-ready assumptions, networking, and commissioning — reviewed by our engineers against your site.